Ice Air VRF

G Series

Ice Air VRF Outdoor G Series 47_47_47

VFOAT-510BRAZA

The Ice Air G Series is the full DC inverter-driven multi-split central air conditioning product. It focuses on customers’ requirements and comfort, representing Ice Air’s high quality and technology. It’s characterized by:

  • High-pressure chamber scroll compressor
  • Integrated high-strength structure and convenient installation
  • Adoption of larger double fans and low-pressure loss heat exchanger
  • Single units range from 6 to 14 tons each; combinations can be achieve 70 tons.
Ice Air VRF G Series Model VFOAT-510BRAZA
Combination VFOAT-170BRATA
VFOAT-170BRATA
VFOAT-170BRATA
Ton 43
Model Power Supply Phase Voltage Hz AC 3-Phase 208/230V 60Hz
Cooling Operation Nominal Capacity Btu/h 512,000
Power Consumption kW 43.1
EER (Btu/h)/W 11.88
Heating Operation Nominal Capacity Btu/h 573,000
Power Consumption kW 41.9
COP W/W 4.01
MCA (Minimum Circuit Ampacity) A 219
MOP (Minimum Overcurrent Protection) A 300
Air Flow Rate CFM 25,423
Overall Dimension (L x W x H) inch (47-5/8+47-5/8+47- 5/8) x 29-17/32 x 68-3/32
Net Weight lbs. 2202
Compressor Quantity 6
Compressor Type Inverter Scroll Hermetic Compressor
Refrigerant Type R410A
Refrigerant Charge Amount lbs. 82.67
Refrigerant Flow Control Micro-computer Control Expansion Valve
Condenser Fan Quantity 3
Cabinet Color Ivory White
Refrigerant Piping Gas Line inch 1-5/8
Liquid Line inch 7/8
Maximum Number of Connectable IDU 64
Maximum Actual Pipe Length Ft. 541
Maximum Equivalent Pipe Length Ft. 623
Height Difference Maximum Below Unit Ft. 164 (295 With Field Setting* )
Maximum Above Unit Ft. 131 (295 With Field Setting*)
Between IDUs Ft. 49 (98 With Field Setting*)
Noise level dB(A) 75
Operation Range Cooling °F DB 23°F~118°F
Heating °F DB -4°F~62°F
*Please contact our technical department at 1-877-ICEAIR (1-877-423-2471) for assistance.
The information contained in this document is subject to change without notice.