The Ice Air 4-Way Cassette allows for flexible refrigerant pipe connections, providing cost effective installation.
| 4-Way Cassette | Model | VFI4C-54BQAKA | |
|---|---|---|---|
| Ton | 4.5 | ||
| Model Power Supply | AC 1-Phase 208/230V 60Hz | ||
| Cooling Operation | Nominal Capacity | Btu/h | 54,600 |
| Power Consumption | kW | 0.13 | |
| Heating Operation | Nominal Capacity | Btu/h | 61,400 |
| Power Consumption | kW | 0.13 | |
| MCA (Minimum Circuit Ampacity) | A | 1.8 | |
| MOP (Minimum Overcurrent Protection) | A | 15 | |
| Air Flow Rate (Hi/Med/Low) | CFM | 1084/1021/904 | |
| Noise Level (Hi/Med/Low) | dB(A) | 41/40/38 | |
| Overall Dimension | Height | inch | 11-11/32 |
| Width | inch | 33-1/16 | |
| Depth | inch | 33-1/16 | |
| Net Weight | lbs. | 57 | |
| Refrigerant Type | R410A | ||
| Refrigerant Flow Control | Micro-computer Control Expansion Valve | ||
| Cabinet Color | Neutral White | ||
| Piping Connections | Flare-nut Connection(with Flare Nuts) | ||
| Refrigerant Piping | Gas Line | inch | 5/8 |
| Liquid Line | inch | 3/8 | |
| Condensate Drain | inch | 1 (Inner Diameter) | |
| Panel Model | IA-G-NK | ||