At 10-1/2 inches high, this space saver easily fits into limited height space requirements, while delivering superior ducted performance.
| Ceiling Ducted (High Static Pressure) | Model | VFICD-54BX2SDH | |
|---|---|---|---|
| Ton | 4.5 | ||
| Model Power Supply | AC 1-Phase 208/230V 60Hz | ||
| Cooling Operation | Nominal Capacity | Btu/h | 54,600 |
| Power Consumption | kW | 0.43 | |
| Heating Operation | Nominal Capacity | Btu/h | 61,400 |
| Power Consumption | kW | 0.43 | |
| MCA (Minimum Circuit Ampacity) | A | 3.5 | |
| MOP (Minimum Overcurrent Protection) | A | 15 | |
| Air Flow Rate (Hi/Med/Low) | CFM | 1377/1095/847 | |
| Noise Level (Hi/Med/Low) | dB(A) | 48/44/38 | |
| Overall Dimension | Height | inch | 11-13/16 |
| Width | inch | 55-1/8+2-15/16 | |
| Depth | inch | 31-1/2 | |
| Net Weight | lbs. | 119 | |
| Refrigerant Type | R410A | ||
| Refrigerant Flow Control | Micro-computer Control Expansion Valve | ||
| Piping Connections | Flare-nut Connection(with Flare Nuts) | ||
| Refrigerant Piping | Gas Line | inch | 5/8 |
| Liquid Line | inch | 3/8 | |
| Condensate Drain | inch | 1 (Inner Diameter) | |
| External Pressure | in. W.G. | 0.5(0.4) | |
| The information contained in this document is subject to change without notice. | |||