Ice Air VRF

H Series

Ice Air VRF Outdoor H Series Small

VFO-28BQAH

Ice Air’s H Series multi-split units incorporate advanced DC inverter technology and provide great product and installation flexibility.
Features include:
• 2 to 10 tons condensers
• Up to 11 indoor units per system
• Dual aerodynamic condenser Fans mean energy savings and low outdoor sound levels
• Wide range of indoor unit types air capacities allows for easy, customized installation

Ice Air VRF H Series Model VFO-28BQAH
Ton 2
Model Power Supply Phase Voltage Hz AC 3-Phase 208/230V 60Hz
Cooling Operation Nominal Capacity Btu/h 27,000
Power Consumption kW 1.93
EER (Btu/h)/W 13.99
Heating Operation Nominal Capacity Btu/h 32,000
Power Consumption kW 2.37
COP W/W 4.01
MCA (Minimum Circuit Ampacity) A 19.5
MOP (Minimum Overcurrent Protection) A 25
Air Flow Rate CFM 1,642
Overall Dimension (L x W x H) inch 40-11/32 x 18-1/8 x 36-5/8
Net Weight lbs. 144
Compressor Quantity 1
Compressor Type Inverter Scroll Hermetic Compressor
Refrigerant Type R410A
Refrigerant Charge Amount lbs. 5.5
Refrigerant Flow Control Micro-computer Control Expansion Valve
Condenser Fan Quantity 1
Cabinet Color Ivory White
Refrigerant Piping Gas Line inch 5/8
Liquid Line inch 3/8
Maximum Number of Connectable IDU 5
Maximum Actual Pipe Length Ft. 82
Height Difference Maximum Below Unit Ft. 66
Maximum Above Unit Ft. 66
Between IDUs Ft. 11
Noise level Cooling/Heating dB(A) 50/52
Operation Range Cooling °F DB 23°F~114.8°F
Heating °F DB -5°F~60°F
The information contained in this document is subject to change without notice.